First Out Indicator
Compact
(Microprocessor)
also known as
First Out Annunciator, First Fault Indicator, First Fault Annunciator, etc.

Part # 0301

(NEW) NOTE: We now offer this in a portable case!

** PLEASE NOTE **

We are sold out of the standalone Compact FOI (#0301), if interested in purchasing quantities of this product please contact us to discuss options.  We do however have portable FOIs available.

Contents
Product Summary
Key Features
Specifications
Overview Diagrams
Ordering Information
Technical Manual
 

Product Summary

 
     A First Out Indicator (FOI) -- also know as First Fault Indicator (FFI) -- is a stand-alone diagnostic tool for non-technical, industrial applications. It is used to monitor a number of electrical contacts, limit switches, push buttons, relays, photo eyes, etc. required to be on for activation of a device e.g. a series string. Should the device stop functioning, the FOI will display the first contact that caused the device to stop running. The FOI provides valuable real-time monitoring to help maintenance personnel resolve intermittent or random shutdown problems. This helps to reduce machine downtime resulting in increase production.

     The FOI was designed to alert operators and/or maintenance crews to the first contact (event) to drop out causing an entire process line to shut down without warning. This allows companies to reduce downtime and increase productivity by immediately notifying operators of process faults for accurate and quick maintenance actions. A process line is defined as equipment in operation using a control circuit with a series of contacts and/or switches that cause the entire process to perform an absolute shut down in the event one contact or switch opens, indicating a failure or a safety violation.

     First Out Indicators are normally found in industrial applications including but not limited to Burner Systems, Printing Presses, HVAC Systems, and Furnaces or other utilize process line configurations. FOI can be used for any application that has an electrical circuit with a number of contacts required for a permissive run. Other, non-industrial uses include display of first respondent in a game show and positive lockout of the other contestants.

Back to Top

Key Features

  • Compact Size for embedded applications
  • 10 Isolated Inputs allows monitoring of contacts from different power sources
  • Power Supply accepts 115 VAC or 230 VAC (auto-select)
  • Remote or on-board RESET and PAST FAULT SELECT
  • Easy to read 7 – Segment LED, 0.44” x 0.81” / 11.2mm x 20.6mm, to indicate the “First Out”
  • 1 Replaceable Isolated Output 2 Channel Solid State Relay for remote display of RUN and HALT (states of operation) These are useful for interfacing with other automation, remote LED or incandescent lamp displays
  • Additional inputs can be added in groups of 10
  • Unit will store and recall previous “First Out”
  • Microprocessor design eliminates false indications due to electrical noise
  • 200K input resistance (50-250V) and 18K (5-50V) assures low circuit loading
  • (Optional) Remote 7-segment LED Display & Bezel

Back to Top

Specifications

  • Monitored inputs rated from 5 to 250 VAC or VDC (depending on configuration)
  • Socketed output Solid State Relay (Opto-coupler) rated from 0 to 250 VAC/VDC 150 mA
  • Resolution time is better than 0.5 millisecond to detect a near simultaneous fault
  • Reaction time is better than 1 millisecond to report a fault via the 7 – Segment LED and Red LED
  • Reaction time is 2 millisecond to activate/deactivate output solid state relay Opto-coupler after a First Out
  • Minimum current flow is 0.25 mA into any input to sense a First Out
  • Operating Temperature Range from -40° C to 85° C
  • Onboard/remote reset with lamp test
  • Power Requirements: 115 VAC or 230 VAC, 3 WATTS (Auto Select)
  • Printed Circuit Board material meets UL 94V-0 requirements
  • Input Resistance (each input):
         ~  50 – 250 VAC or VDC is 200K
         ~  5 – 50 VAC or VDC is 18K
  • Dimensions:
         ~  4.5” x 4.5” x 1” US
       
     ~  (11.4cm x 11.4cm x 2.5cm)
  • (Optional) Remote 7-segment LED Display Bezel
         ~  Overall Size:
                   --  2” x 1.375” x 1” US
                   --  (5.1cm x 3.5cm x 2.5cm)
         ~  Clearance Hole:
                   --  1.587” x 1.114” US
                   --  (4.03cm x 2.83cm)

Back to Top

Overview Diagrams

First Out Indicator Compact
Part # 0301

Click here to view board layout

 Back to top

Ordering Information

To place an order for the First Out Indicator Compact; Part # 0301 in quantities click here to contact us.

Back to Top

Industrial Solutions / Audio Solutions / Custom Solutions

Updated! Audio Equipment  (Repair Service, Prototype Vacuum Tube Amps, etc)

NEW Portable First Out Indicator (FOI)

Contact Us / Home

Copyright© 1999-2008  1212 Designs. All rights reserved.