Product Summary
Key Features
Specifications
Overview Diagrams
Ordering Information
Technical Manual
 

Product Summary

 
     The First Out Indicator (FOI) was designed to alert operators and/or maintenance crews to the first contact (event) to drop out causing an entire process line to shut down without warning.  Therefore, eliminating guesswork of which device contact opened first initiating the shutdown of the equipment, this helps to reduce the downtime of production equipment.  A process line is defined as equipment in operation using a control circuit with a series of contacts and/or switches that cause the entire process to perform an absolute shut down in the event one contact or switch opens, indicating a failure or a safety violation.
 

     First Out Indicators are normally found in industrial applications such as Burner Systems, Printing Presses, HVAC System, Furnaces, etc that utilize this type configuration.  FOI can be used for any application that has an electrical circuit with a number of contacts required for a permissive run. Other, non-industrial uses might include display of first respondent in a game show and positive lockout of the other contestants.

Back to Top

Key Features

  • 10 Isolated Inputs, to allow monitoring of contacts from different power sources
  • Power Supply can accept 115VAC or 230VAC (switch-selectable)
  • Remote or on-board RESET and PAST FAULT SELECT
  • Customer contacts, Form "C" rated 12 Amps 120 VAC, 12 Amps 24 VDC, are useful for sounding remote alarms, stopping or starting related processes, etc.
  • Easy to read 7 - Segment LED, 0.44" x 0.81" / 11.2mm x 20.6mm, to indicate the "First Out"
  • 11 Replaceable Isolated Output Solid State Relays for remote display of the "First Out" and fault conditions (common ground) These are useful for interfacing with other automation, remote LED or incandescent lamp displays
  • Additional inputs may be added in groups of 10
  • Unit will store and recall previous "First Out"
  • Microprocessor design eliminates false indications due to electrical noise
  • 200K input resistance (50-250V) and 18K (5-50V) assures low circuit loading
  • Quick-Connect terminal blocks for quick removal of external connections

Back to Top

Specifications

  • Monitored inputs rated at 5 - 250V AC or DC (depending on configuration)
  • Socketed output Solid State Relays (opto-couplers) rated at 0 - 250 VAC/DC 150 mA
  • Service Contacts rated at 12 Amps 120 VAC, 12 Amps 24 VDC
  • Resolution time to detect a near simultaneous fault is better than 0.5 millisecond
  • Reaction time to report a fault via the 7 - Segment LED and Red LED is better than 1 millisecond
  • Reaction time to release Customer Contacts after a fault 2 millisecond
  • Minimum current flow into any input to sense a First Out is 0.25 mA
  • Operating Temperature Range: -40° C to 85° C
  • Onboard/remote reset with lamp test
  • Power Requirements: 115VAC or 230VAC, 3 WATTS
  • Printed Circuit Board material meets UL 94V-0 requirements
  • Input Resistance (each input):
         ~ 50 - 250V AC or DC is 200K
         ~ 5 - 50V AC or DC is 18K
  • Dimensions:
         ~ 9 ¼" x 7 ¾" x 1 ¼" US
         ~ 23.5cm x 19.7cm x 3.2cm

Back to Top

Overview Diagrams

First Out Indicator Version 2
Part # 0206

Click here to view board layout

 Back to top

Ordering Information

To place an order for the First Out Indicator Version 2; Part # 0206, click here to contact us.

Back to Top

Industrial Solutions / Audio Solutions / Custom Solutions

NEW Portable First Out Indicator (FOI)

Try our Audio Equipment Repair Service

Contact Us / Home

Copyright© 1999-2008  1212 Designs. All rights reserved.